Section 903.3.1.3.2 is added to read as follows:

903.3.1.3.2 Each water system supplying both domestic and fire protection systems shall have a single indicating-type control valve, arranged to shut off both the domestic and sprinkler systems. A separate shut-off valve for the domestic system only shall be permitted to be installed. The location of the control valve shall be approved by the fire code official.

(Ord. 2022-06 § 1 (Exh. A), 2022)