Section 903.3.1.3.1 is added to read as follows:

903.3.1.3.1 All fire sprinkler systems installed in one- and two-family dwellings shall be tested for leakage by undergoing a hydrostatic test made at 200 psi for two-hour duration.

(Ord. 2022-06 § 1 (Exh. A), 2022)