Section 907.7.2 is amended to read as follows:

907.7.2 Completion documents. The following documentation shall be provided at the time of acceptance testing for all fire alarm system installations:

1. A record of completion in accordance with NFPA 72.

2. A contractor’s statement verifying that the system has been installed in accordance with the approved plans and specifications and has been 100% tested in accordance with NFPA 72.

3. A contractor’s affidavit of personnel qualifications, indicating that all personnel involved with the installation of the fire alarm system meet the qualification requirements of the fire code official.