Section 903.3.1.3.7 is added to read as follows:

903.3.1.3.7 Automatic fire sprinklers shall be installed to protect all furnaces and heating system appliances.

MARINA CITY FIRE CODE INTERPRETATION

With regards to requiring fire sprinkler installation in bathrooms,

Do rooms with toilets and/or bidets only and no electrical receptacles require fire sprinklers?

ANSWER: No unless they exceed the 55 square foot minimum in NFPA 13R and NFPA 13D.

Do rooms with showers only and no electrical receptacles require fire sprinklers?

ANSWER: No, unless they exceed the 55 square foot minimum in NFPA 13R and NFPA 13D.

(Ord. 2022-06 § 1 (Exh. A), 2022)