Skip to main content
Loading…
This section is included in your selections.

Section 903.2 is amended to read as follows:

903.2 Where required. Approved automatic sprinkler systems shall be provided in all new buildings and structures constructed, moved into, or relocated within the jurisdiction.

Exceptions:

(1) Structures not classified as Group R occupancies and not more than five hundred (500) square feet in total floor area.

(2) Detached agricultural buildings, as defined by this code and the CBC, located at least one hundred feet (100) from any other structure or the property line, whichever is closer.

(3) Accessory structures not classified as R occupancies associated with existing non-sprinklered R-3 occupancies (one- or two-family dwellings) and less than one thousand five hundred (1500) square feet in total fire area.

(4) Where an insufficient water supply exists to provide for an automatic fire sprinkler system and where the Fire Code Official permits alternate protection.

The following sections are amended by changing requirements to five hundred square feet for fire sprinkler installation, as follows (the complete text of the section is not provided):

903.2.1.1 Group A-1. Change twelve thousand (12,000) square feet to five hundred (500) square feet.

903.2.1.2 Group A-2. Change five thousand (5,000) square feet to five hundred (500) square feet.

903.2.1.3 Group A-3. Change twelve thousand (12,000) square feet to five hundred (500) square feet.

903.2.1.4 Group A-4. Change twelve thousand (12,000) square feet to five hundred (500) square feet.

903.2.1.5 Group A-5. Change one thousand (1,000) square feet to five hundred (500) square feet.

903.2.3 Group E. Change twelve thousand (12,000) square feet to five hundred (500) square feet.

903.2.4 Group F-1. Change twelve thousand (12,000) square feet to five hundred (500) square feet.

903.2.4.1 Group F-1. Change two thousand five hundred (2,500) square feet for woodworking operations to five hundred (500) square feet.

903.2.7-1 Group M. Change twelve thousand (12,000) square feet to five hundred (500) square feet.

903.2.7-3 Group M. Change twenty-four thousand (24,000) square feet to five hundred (500) square feet.

903.2.9 Group S-1. Change twelve thousand (12,000) square feet to five hundred (500) square feet.

903.2.9.1 Repair Garages. Change ten thousand (10,000) square feet (2 story buildings) and twelve thousand (12,000) square feet (1 story buildings) to five hundred (500) square feet.

903.2.9.2 Bulk storage of tires. Change twenty thousand (20,000) cubic feet to five hundred (500) square feet.

(Ord. 2022-06 § 1 (Exh. A), 2022)